Item # HX-227F30J, 227 Series Explosion-Proof Duct Heaters


  • CSA Approved for virtually all Class I and Class II, Division 1 and 2 hazardous gas or dusty atmospheres
  • Ignition temperatures as low as 320°F (160°C)
  • Six standard sizes to fit a wide range of ducts with twenty four available sizes.
  • Ratings up to 240 kW, 600 volts






Specifications  · Temperature Control

Specifications

Unit Size Code

J

Min. Duct Power

20 kW

Max. Duct Power

60 kW

Min. Inside Duct Dimensions (W x H)1

21 x 21 inches
53.3 x 53.3
cm

Max. Inside Duct Dimensions (W x H)2

37 x 35 inches
94 x 89
cm

Depth

24 inches

Weight

400 lb

Custom Options

View
C - Corrosion Resistant Construction
D - Built-on Disconnect Switch

F - Supplementary Fusing

G - NEMA 4 Construction

K - "Warning" Pilot Light

L - "Heater On" Pilot Light

M - Disconnecting Magnetic Contactors

P - Built-on Airflow Switch

V - 120 Volt Control Circuit

Z - Group B Construction
1 Use only Minimum W x H dimensions for minimum air velocity calculations.
Duct height and width can vary independently of minimum and maximum dimensions.
2 Consult factory for availability of other maximum inside duct dimensions.
Duct height and width can vary independently of minimum and maximum dimensions.


Temperature Control
    Single Stage Control - For many lower KW applications, single stage on/off control is adequate. For higher KW ratings, solid-state SCR control is recommended.

    Solid-State SCR Control - When temperature must be controlled precisely, or for larger kW heaters, built-in SCR’s are recommended. They are furnished with field-selected inputs of 2200 or 135 ohms, 0-10 VDC, or 4-20 mA. SCR's have zero-cross firing to eliminate radio frequency interference.
    To meet FM and CSA requirements, multi-unit designs (up to four heating units in series) also have controls set at 80°F (27°C) to limit the inlet air temperature to all but the inlet unit. These limit controls prevent excessive temperatures at the heater outlet as the inlet air temperature rises.